STANDBY |
|
|
If the device was not switched off while in lockout, the operating cycle resumes at the next switch-on, unless it is configured so that an intentional start-up is always required: in this case it remains in stand-by until reset from local push button. The fuel valves are off while the behaviour of the air valve and the position of the actuator can be defined. The air pressure switch can be enabled to detect air failure or air simulation, depending on air output setting. |
|
|
Response time of the air pressure switch is adjustable to tolerate short events. |
|
|
Allowed remote commands S s A a O o f L D d Dxx |
|