CYCLIC COMMUNICATION


The content and scope of the communication between Q2 (device) and the automation system (controller) can be freely defined as required. For this purpose, you can select the individual modules available for data communication from the structure offered in the GSD file.

The modules are placed in the slots predetermined by the system. All modules required for cyclic data communication with Q2 are shown in the following table.



MODULE

SLOT

Input address

Output address

1

Control

1

n n+1

n n+1

2

Inputs/outputs

2

n n+1


3

Flame signal

3

n


4

Actuator

4

n

n

5

Display

5

n n+1


6

Configuration

6

n

n


SLOT 1

CONTROL MODULE

 DEVICE → CONTROLLER


BIT

CURRENT STATUS

FORMAT

NOTE

BYTE n

0

DEVICE ON

BOOL

Q2 connected and responding

1

STANDBY

BOOL

The device is in STANDBY

2

LOCKOUT

BOOL

The device is in LOCKOUT

3

VPS FAILURE

BOOL

Lockout due to leakage test failure

4

MANUAL SHUTDOWN

BOOL

Device has been put out of service locally

5

CONTROLLED SHUTDOWN

BOOL

Burner was turned off upon request

6

AIR PRESSURE WAITING

BOOL

The cycle is waiting for air pressure

7

POST-COMBUSTION

BOOL

Burner off waiting for the flame quenching

BYTE n+1

0

PRE-OPERATION

BOOL

Valve proving and pre-purge in progress

1

IGNITION

BOOL

Burner ignition in progress

2

STAGE 2

BOOL

Burner on, stage 2 low temperature

3

STAGE 3

BOOL

Burner on, stage 3 low temperature

4

STAGE 4

BOOL

Burner on, stage 4 low temperature

5

STAGE 5

BOOL

Burner on, stage 5 high temperature

6

STAGE 6

BOOL

Burner on, stage 5 high temperature

7

POST-OPERATION

BOOL

Valve proving and post-purge in progress



SLOT 1

CONTROL MODULE

CONTROLLER → DEVICE


BIT

Command

Action

FORMAT

BYTE n

0

UNLOCK

Set to1 and then to 0, emulating a push button, to reset from lockout

BOOL

1

RUN

0 = stop burner

1 = start burner 1

BOOL

2

AIR OUTPUT

0 = air valve output OFF

1 = air valve output ON 2

BOOL

3

OS OUTPUT

0 = shutter output OFF

1 = shutter output ON 3

BOOL

4

HT confirmation

Confirm the request for indirect flame surveillance (high temperature mode) 4

BOOL

5

CFG LED

Orange indicator

BOOL

6

OUTPUT 1

0 = output 1 OFF

1 = output 1 ON

BOOL

7

OUTPUT 2

0 = output 2 OFF

1 = output 2 ON

BOOL

BYTE n+1

0

NONE

No forced stage, cycle deploys normally 

BOOL

1

STAGE 2

Move to stage 2 5

BOOL

2

STAGE 3

Move to stage 3 5

BOOL

3

STAGE 4

Move to stage 4 5

BOOL

4

STAGE 5

Move to stage 5 5

BOOL

5

STAGE 6

Move to stage 6 5

BOOL

6

NOT USED


BOOL

7

NOT USED


BOOL


1        No effect if the device is in LOCKOUT or MANUAL SHUTDOWN.

2        If allowed in the current stage.

3        Generic output, if not used for optical shutter control.

4        If required by configuration (parameter G08) activate periodically within 5 minutes.

5        If bits 1 to 5 are set simultaneously, the priority is always the lower one.


SLOT 2

INPUTS/OUTPUTS MODULE

DEVICE → CONTROLLER


BIT

DESCRIPTION

FORMAT

NOTE

BYTE n

0

AIR PRESSURE SWITCH INPUT

BOOL

0 = insufficient air pressure

1 = air pressure OK 

INPUTS (STATUS)

1

FUEL PRESSURE SWITCH INPUT

BOOL

0 = insufficient fuel pressure

1 = fuel pressure OK

2

HT INPUT

BOOL

0 = High temperature mode

1 = Low temperature mode 

3

NOT USED

BOOL

always 0

4

NOT USED

BOOL

always 0

5

NOT USED

BOOL

always 0

6

INPUT 1

BOOL

0 = input off

1 = input on

7

INPUT 2

BOOL

0 = input off

1 = input on

BYTE n+1

0

AIR OUTPUT

BOOL

0 = air valve VA off

1 = air valve VA on 

OUTPUTS S (TATUS)

1

VS OUTPUT

BOOL

0 = fuel valve VS off

1 = fuel valve VS on

2

VB OUTPUT

BOOL

0 = fuel valve VB off

1 = fuel valve VB on

3

V1 OUTPUT

BOOL

0 = fuel valve V1 off

1 = fuel valve V1 on

4

V2 OUTPUT

BOOL

0 = fuel valve V2 off

1 = fuel valve V2 on

5

OS OUTPUT

BOOL

0 = shutter output off

1 = shutter output on

6

OUTPUT 1

BOOL

0 = output 1 off

1 = output 1 on

7

OUTPUT 2

BOOL

0 = output 2 off

1 = output 2 on


SLOT 3

FLAME SIGNAL MODULE

DEVICE → CONTROLLER


BIT

DESCRIPTION

FORMAT

NOTE

BYTE n

0

Flame 1 signal

DEC

0…99 (255) µA

1

2

3

4

5

6

7

BYTE n+1

0

Flame 2 signal

DEC

0…99 (255) µA

1

2

3

4

5

6

7


SLOT 4

ACTUATOR

DEVICE → CONTROLLER


BIT

DESCRIPTION

FORMAT

NOTE

BYTE n

0

Current actuator position

DEC

0…100 (255)

0…100%

1

2

3

4

5

6

7


SLOT 4

ACTUATOR

CONTROLLER → DEVICE


BIT

DESCRIPTION

FORMAT

NOTE

BYTE n

0

Required actuator position

DEC

0…100 (255)

1

2

3

4

5

6

7


SLOT 5

DISPLAY

DEVICE → CONTROLLER


BIT

DESCRIPTION

FORMAT

NOTE

BYTE n

0

Current RED display

HEX

00…FF

1

2

3

4

5

6

7

BYTE n+1

0

Current BLUE display

HEX

00…FF

1

2

3

4

5

6

7


SLOT 6

SETTINGS MODULE

 CONTROLLER → DEVICE


BIT

CURRENT STATUS

FORMAT

NOTE

BYTE n

0

NOT USED

BOOL

0

1

NOT USED

BOOL

0

2

PROFINET DISCONNECT

BOOL

0: CONTINUE USING LAST CONDITION

1: BURNER OFF (HALT)

3

PROFINET NOT CONFIGURED

BOOL

4

NOT USED

BOOL


5

NOT USED

BOOL


6

NOT USED

BOOL


7

NOT USED

BOOL



SLOT 6

CONFIGURATION MODULE

 DEVICE → CONTROLLER


BIT

CURRENT STATUS

FORMAT

NOTE

BYTE n

0

NOT USED

BOOL

0

1

NOT USED

BOOL

0

2

PROFINET DISCONNECT

BOOL

0: CONTINUE USING LAST CONDITION

1: BURNER OFF (HALT)

3

PROFINET NOT CONFIGURED

BOOL

4

TRANSPARENT MODE

BOOL

0: DISABLED

1: ENABLED 1

5

NOT USED

BOOL


6

NOT USED

BOOL


7

NOT USED

BOOL



1        When TRANSPARENT MODE is enabled, inputs to the controller are rendered, but all
       outputs sent from the controller to the device are ignored. 
       This mode is enabled/disabled from webserver interface.