COMMANDS

TraxBus and optical interfaces share the same protocol.

For the internal optical interface, addressing does not apply, therefore S and N are ignored (they can assume any value), the response will be returned using the same address specified in the command.


COMMANDS

EXAMPLE

H

HALT

GO TO CONTROLLED SHUTDOWN, IF NOT IN LOCKOUT

<00HF1\r

R

RUN

EXIT CONTROLLED SHUTDOWN

<00RFB\r

B

UNLOCK §1

RESET FROM LOCKOUT, TO BE CONFIRMED WITHIN 10 SECONDS

<00BEB\r

Y

CONFIRM §1

IGNORED WHEN NOT RECEIVED AFTER UNLOCK COMMAND B

<00Y02\r

a

AIR OFF

TURN OFF AIR VALVE OUTPUT

<00a0A\r

A

AIR ON

TURN ON AIR VALVE OUTPUT

<00AEA\r

o

OS OFF

TURN OFF OS OUTPUT, IF NOT USED TO DRIVE UV OPTICAL SHUTTER

<00o18\r

O

OS ON

TURN ON OS OUTPUT, IF NOT USED TO DRIVE UV OPTICAL SHUTTER

<00OF8\r

f

HIGH TEMPERATURE CONFIRMATION

ENABLE HT INPUT FOR 5 MINUTES (SEE PARAMETER G08)

<00f0F\r

I

IGNITION TRIAL

GOTO PREIGNITION (FOR THE STAGES THAT ALLOW THE TRANSITION) 

<00IF2\r

2

STAGE 2

GOTO STAGE 2 (FOR THE STAGES THAT ALLOW THE TRANSITION) 

<002DB\r

m

STAGE 2

SAME AS ABOVE (KEPT FOR COMPATIBILITY) 

<00m16\r

3

STAGE 3

GOTO STAGE 3 (FOR THE STAGES THAT ALLOW THE TRANSITION) 

<003DC\r

M

STAGE 3

SAME AS ABOVE (KEPT FOR COMPATIBILITY) 

<00MF6\r

4

STAGE 4

GOTO STAGE 4 (FOR THE STAGES THAT ALLOW THE TRANSITION) 

<004DD\r

5

STAGE 5

GOTO STAGE 5 (FOR THE STAGES THAT ALLOW THE TRANSITION) 

<005DE\r

6

STAGE 6

GOTO STAGE 5 (FOR THE STAGES THAT ALLOW THE TRANSITION) 

<006DF\r

S

STATUS

NO ACTION, SHORT STATUS REQUEST

<00SFC\r


§1

THE SUPERVISOR MUST SEND A RESET CONFIRMATION WITHIN 10 SECONDS FROM PERIPHERAL
ACKNOWLEDGE TO RESET COMMAND.



For each command received, the device returns a code corresponding to its current status, the status codes are listed below:



SHORT STATUS CODES

EXAMPLE

S

STOP §2

LOCKOUT OR FAILURE

>00SFE\r

0

MANUAL SHUTDOWN

THE UNIT HAS BEEN PUT OUT OF SERVICE USING THE LOCAL BUTTON

>000DB\r

T

TIGHTNESS FAILURE

UNSUCCESSFUL VALVE PROVING 

>00TFF\r

h

HALT

POWER ON STANDBY, WAITING FOR UNLOCK TO START

>00h13\r

H

HALT

CONTROLLED SHUTDOWN

>00HF3\r

A

AIR PRESSURE WAITING

WAITING FOR AIR PRESSURE DURING PREPURGE OR POSTPURGE

>00AEC\r

P

PRE-OPERATION

PREPURGE / VALVE PROVING (IF ENABLED)

>00PFB\r

1

IGNITION

INCLUDING PRE-IGNITION

>001DC\r

2

STAGE 2

BURNER ON, LOW TEMP MODE STAGE 2

>002DD\r

3

STAGE 3

BURNER ON, LOW TEMP MODE STAGE 3

>003DE\r

4

STAGE 4

BURNER ON, LOW TEMP MODE STAGE 4

>004DF\r

5

STAGE 5

BURNER ON, HIGH TEMP MODE STAGE 5

>005E0\r

6

STAGE 6

BURNER ON, HIGH TEMP MODE STAGE 6

>006E1\r

Y

POSTCOMBUSTION

WAITING FOR FLAME QUENCHING 

>00Y04\r

W

POST-OPERATION

POSTPURGE / VALVE PROVING (IF ENABLED)

>00W02\r


§2

alL LOCKOUTS AND FAILURES ARE GROUPED WITHIN A SINGLE CODE TO SIMPLIFY THE PARSING. DETAILED
INFORMATION AVAILABLE FROM THE FRONT PANEL DISPLAY.
ADDITIONAL INFORMATION BY READING THE LOG FILE STORED IN THE UNIT



A specific command returns the current value of the FLAME SIGNAL according to the settings of parameter G06:



COMMAND

EXAMPLE

L

FLAME SIGNAL

ASK FOR FLAME SIGNAL STRENGTH, KEPT FOR COMPATIBILITY

<00LF7\r


The answer is rendered in a single character



STATUS CODE

EXAMPLE

a…z

FLAME SIGNAL

−        0 µA
a…y        1…25 µA
z        26 µA OR HIGHER

>00y24\r




ACTUATOR CONTROL

The ACTUATOR can be managed by means of the following specific commands:



COMMANDS

EXAMPLE

D

AIR DAMPER POSITION

RETURNS CURRENT ACTUATOR POSITION (%)

<00DED\r

d

AIR DAMPER POSITION (ABSOLUTE)

RETURNS CURRENT POTENTIOMETER MEASURED VALUE (0000…4095)

<00d94\r

DCL

CLOSE

ACTIVATE CLOSE OUTPUT PERMANENTLY (UNTIL DST OR LO POSITION)

<00DCL7C\r

DOP

OPEN

ACTIVATE OPEN OUTPUT PERMANENTLY (UNTIL DST OR HI POSITION)

<00DOP8C\r

DST

STOP

RELEASE OPEN AND CLOSE OUTPUTS IMMEDIATELY

<00DST94\r

Dxx

MOVE TO POSITION

SET NEW POSITION FOR THE ACTUATOR: LO | 01…99 | HI

<00D5052\r


The answer is always the current position of the actuator:



STATUS CODE

EXAMPLE

Dxx

AIR DAMPER POSITION

THIS IS THE ANSWER TO ALL DAMPER CONTROL COMMANDS EXCEPT d

LO        0% (CORRESPONDING TO CLOSED LIMIT SWITCH)
01…99        CURRENT RELATIVE POSITION %
HI        100% (CORRESPONDING TO OPEN LIMIT SWITCH)

>00D5054\r

dxx

AIR DAMPER POSITION (ABSOLUTE)

THIS IS THE ANSWER TO COMMAND d

00…FF        ABSOLUTE VALUE READ BY FEEDBACK POTENTIOMETER

>00d006F\r


Request for current actuator settings.



COMMANDS

EXAMPLE

DDR

AIR DAMPER SETTINGS

RETURNS ACTUATOR LIMITS AND TRAVEL TIME:
LO,HI,T,1,99

LO        ABSOLUTE POSITION OF LO LIMIT SWITCH (0%)
HI        ABSOLUTE POSITION OF HI LIMIT SWITCH (100%)
T        TRAVEL TIME FROM MIN TO MAX (seconds)
1        ABSOLUTE POSITION OF MIN POTENTIOMETER RANGE (1%)
99        ABSOLUTE POSITION OF MAX POTENTIOMETER RANGE (99%)

<00DDR83\r




EXTENDED STATUS

When the supervisor is able to interpret complex responses, it is possible to use the command which returns an EXTENDED status:



COMMAND

EXAMPLE

s

STATUS REQUEST (EXTENDED)

NO ACTION, EXTENDED STATUS REQUEST

<00s1C\r


The response is rendered in a single string including multiple information, comma delimited:



EXTENDED STATUS CODE FIELDS

EXAMPLE


PREAMBLE

>


IDENTIFIER (SEGMENT + NODE)

00

STEP

SHORT STATUS CODE (SAME AS S RESPONSE)

2

DAMPER

CURRENT POSITION OF THE ACTUATOR (0=LO | 1 … 99 | 100=HI)

30

damper

CURRENT ABSOLUTE POSITION OF THE ACTUATOR (00 … FF)

38

FL1

CURRENT FLAME 1 SIGNAL (0 … 30) [µA]

0

FL2

CURRENT FLAME 1 SIGNAL (0 … 30) [µA]

0

HT

HIGH TEMPERATURE INDIRECT FLAME SURVEILLANCE (0=NO | 1=YES)

1

AIRPRESS

AIR PRESSURE SWITCH STATUS (0=OPEN | 1=CLOSED)

1

GASPRESS

GAS PRESSURE SWITCH STATUS (0=OPEN | 1=CLOSED)

1

VA

AIR VALVE OUTPUT (0=OFF | 1=ON)

1

VS

SAFETY FUEL VALVE VS OUTPUT (0=OFF | 1=ON)

0

VB

BYPASS FUEL VALVE VB OUTPUT (0=OFF | 1=ON)

1

V1

PILOT FUEL VALVE V1 OUTPUT (0=OFF | 1=ON)

0

V2

MAIN FUEL VALVE V2 OUTPUT (0=OFF | 1=ON)

0

OS

OS OUTPUT (0=OFF | 1=ON)

0

DISPL1

CONTENT OF RED DISPLAY (ASCII FIGURE OF HEX CODE (00 … FF)

DA

DISPL2

CONTENT OF BLUE DISPLAY (ASCII FIGURE OF HEX CODE (00 … FF)

C4


>00,2,30,38,0,0,1,1,1,1,0,1,0,0,0,DA,C489\r


The checksum is calculated including all data and commas + carriage return.