Complements
High performance UV detector for flame detection in gas, oil and mixed burners together with suitable Burner Control Unit or Flame Amplifier Device
TECHNICAL
DATA
SENSOR
SPECTRAL RESPONSE185...260 nm
OPERATING VOLTAGE200...280 Vac
DISCHARGE CURRENT1 mA
PEAK DISCHARGE CURRENT30 mA
RECOVERY TIME20 µs
ENVIRONMENT
OPERATING TEMPERATURE-25...125°C
PEEPSIGHT TEMPERATURE125°C MAX
MAX VIBRATION ALLOWED0,5 g
RELATIVE HUMIDITY10...90%
PROTECTION CLASSIP65
DIMENSIONAL DATA
INSULATING CASEØ35 x 80 mm
ELECTRIC CONNECTION3 pole SOCKET
WIRE GAUGE2 x 1,5 mm²
MECHANICAL CONNECTION¾ GAS
COOLING CONNECTION¼ GAS
MOUNTING POSITIONANY
WEIGHT150 g MAX
OPERATING LIFE>10.000 hours @ 50°C
UP TO 100.000 hours @ 50°C WHEN COUPLED WITH CONTRIVE DEVICES
LITERATURE
UTILITIES
WIRING
WIRING DIAGRAM
01 - POSITIVE TERMINAL
01 - USUALLY GROUND
02 - NEGATIVE TERMINAL
02 - USUALLY AMPLIFIER INPUT
REVERSED POLARITY DOES NOT DAMAGE THE DETECTOR BUT PRODUCES NO USEFUL FLAME SIGNAL
CLASS II DEVICE
NO CONNECTION TO PROTECTION GROUND REQUIRED
DIMENSION
TYPICAL
PERFORMANCE
SPECTRAL RESPONSE
SENSITIVITY vs. SUPPLY VOLTAGE
VERTICAL DIRECTIVITY
HORIZONTAL DIRECTIVITY