F808 – HI-TEMP BYPASS TC CONFIRM
DISABLED ‹
ENABLED ‹
Instead of using redundant control on high temperature flame surveillance bypass, the local thermocouple can operate as a second channel confirmation.
When this option is enabled, the bypass will be activated only when the local thermocouple input confirms that the temperature is above 750°C.